Solar Energy, A Complement To FTA (2782401 Views)
mctfopt: 1:58pm On Mar 16 |
ask4bk: Parallel Wiring: If the s have similar voltages, connect them in parallel. This method adds the currents while maintaining the voltage, maximizing the total power output. Series Wiring: If the s have different voltages, connecting them in series can increase the total voltage. However, this method is less efficient for mixed-wattage s as it uses the lowest current, potentially reducing overall power output 2 Likes |
mctfopt: 1:59pm On Mar 16 |
HeavenlyBang: Battery may have been used for 7 years. Lol 1 Like |
Dam5reey1(m): 2:31pm On Mar 16 |
ask4bk: Same Voltage or less than 5% difference = parallel Same Current or less than 5% difference = Series. Jinko 440w and 555w works perfectly in Series.. I have shared this on my older name before. 5 Likes |
ksmart027(m): 2:38pm On Mar 16 |
HeavenlyBang:You don leave us for cartalk, wetin dey happen na ![]() ![]() |
Anyone0455: 3:08pm On Mar 16 |
So here is the thing I have addo and sunfit battery both 220ah Tho I just added the sunfit battery to the addo but I noticed the life span is not different from when I was using the single addo battery I’m now thinking is it the inverter cause the inverter is 900kva addo |
andymola(m): 3:41pm On Mar 16 |
HeavenlyBang: I really appreciate this. Please can I have your number |
HeavenlyBang(m): 4:11pm On Mar 16 |
ksmart027: I still dey, boss. There's just not much going on in Cartalk anymore unfortunately, but I try to check in regularly and contribute when I can. ![]() 2 Likes |
HeavenlyBang(m): 4:11pm On Mar 16 |
jceesquare(m): 4:15pm On Mar 16 |
HeavenlyBang:Like once in 2 years ![]() |
HeavenlyBang(m): 5:07pm On Mar 16 |
jceesquare: Cartalk is almost dead because cars are so expensive now. Economy don hold men for neck ![]() 7 Likes |
ask4bk(m): 5:25pm On Mar 16 |
Dam5reey1:Thanks.. They are actually both jinko 555w but but have shattered glass. One is producing 250w, don't know about the other yet. Both being shattered at different degrees I only thought they will now have different volts and current production. I want to both together for a setup. I can still use them for some years. |
Christian8880: 7:34pm On Mar 16 |
5kwh 51.2v felicity lithium batteries available Price-#1,350,000 Call or WhatsApp me on 09116033581
|
jceesquare(m): 9:03pm On Mar 16 |
HeavenlyBang:True sa |
Oshomo12(m): 9:08pm On Mar 16 |
ask4bk: Guys be very careful with all this shattered glass solar s. They discard them for a reason. Some people may have been using them for years here, well, I don't joke with myself and properties. The money saved in buying them is not worth the risk. |
Oshomo12(m): 9:23pm On Mar 16 |
HeavenlyBang: I have said it here over times, you don't sell a used battery!!! Except you know for certain the state of health of the battery. I may part with 100k for one. 400k!! You be father Christmas now. 1 Like |
ksmart027(m): 10:33pm On Mar 16 |
HeavenlyBang:Na true sha. Much respect boss. 1 Like |
primeelectronix: 7:26am On Mar 17 |
AUTHORIZED DEALER ON JINKO SOLAR ,GROWATTS INVERTER&BATTERIES,FIRMAN INVERTERS&BATTERIES,CENTURY INVERTERS AND PYLONTECH LITHIUM ION BATTERIES AND MORE AVAILABLE ITEMS RIGHT NOW!!!!!!!!!!!!!! 450WATTS JINKO SOLAR S 475WATTS JINKO SOLAR S 485WATTS JINKO SOLAR S 555WATTS JINKO SOLAR S 560WATTS JINKO SOLAR S 590WATTS JINKO SOLAR S 615WATTS JINKO SOLAR S 620WATTS JINKO SOLAR S HUAWEI...ALL IN ONE SOLAR SYSTEMS POWER M INVERTER AND LITHIUM BATTERIES GROWATTS INVERTERS SPF 3000TL HVM 48 SPF 5000TL HVM P SPF 3500ES SPF 5000ES SPF 6000ES SPH 3600TL BL UP SPH 5000TL BL UP SPH 8000TL3 BH UP SPH 10000TL3 BHUP DEYE INVERTERS AVAILABLE DEYE 8KW HYBRID INVERTER THREE PHASE,LOW VOLTAGE DEYE 12KW HYBRID INVERTER THREE PHASE,LOW VOLTAGE DEYE 50KW HYBRID INVERTER THREE PHASE,HIGH VOLTAGE PYLONTECH LITHIUM ION BATTERIES UP5000 5.12KWH 100AH HORIZONTALAND VERTICAL BRACKET FOR ALL MODELS OF BATTERIES EXTERNAL CABLE KIT FOR USC(CONNECT BATTERY TO INVERTER ALSO AVAILABLE FIRMAN 550WATTS SOLAR S 410 WATTS SOLAR S.. FIRMAN HYBRID INVERTERS 1KVA HYBRID TRANSFORMER INVERTERS 3KVA HYBRID TRANSFORMER INVERTERS 5KVA HYBRID TRANSFORMER INVERTERS 3KVA HYBRID TRANSFORMERLESS INVERTERS 5KVA HYBRID TRANSFORMERLESS INVERTERS FIRMAN LITHIUM ION BATTERIES 5KWH 25.6V 200AH LITHIUM ION BATTERIES 5KWH 51.2V 100AH LITHIUM ION BATTERIES 10KWH 51.2V 200AH LITHIUM ION BATTERIES BEST QUALITY CENTURY HYBRID INVERTERS 1.2KVA HYBRID INVERTERS 2.2KVA HYBRID INVERTERS 3.2KVA HYBRID INVERTERS SUNTREE AC/DC BREAKERS SUNTREE SURGE PROTECTORS SUNTREE AC GUARD SUNTREE DC ISOLATORS SUNTREE MCCB SUNTREE ENCLOSURE BOXES SUNTREE MC4 SUNTREE DISTRIBUTION BOXES AND MANY MORE. ALL ITEMS ARE VERY MUCH AVAILABLE AND WILL BE DELIVERED WITH EASE.. NO NEED TO RUN TO ARENA OR ALABA ANYMORE... WE ARE HERE TO SERVE YOU SO WELL... PRICES ARE FRIENDLY CALLING NUMBER...08088331608/09074488146 OR SEND WHATSAPP MESSAGE WITH THE SAME NUMBER... WE ARE VERY ACTIVE.... TO ALL THE SOLAR ENGINEERS,KINDLY BRING DEALS AND A WARMFUL DISCOUNT AWAITS YOU. 1 Like 1 Share |
ask4bk(m): 8:11am On Mar 17 |
Oshomo12:I appreciate the advice sir. But I didn't buy them shattered. I bought them brand new, and while transporting to far location on bad road with ups and down, 2 s shattered out of 10. I used the 8 clean one. The other 2 are still producing power. I don't want to waste them when I've extra inverter, extra controller I can throw the two shattered ones into to help me get the value of the money I spent on them. Can't throw 260k away like that. They can serve me for 5-8 yrs if I'm lucky. 1 Like |
Amyah: 9:42am On Mar 17 |
Good morning, everyone. Please, I need some advice or information concerning an issue. I have a 2.5kva inverter system that was installed November, 2024. All was well until Feb/March 2025. My inverter now trips off once the sun goes down after about like 5-6 hours of use. When I charge it with nepa, it reaches 14.6, one time I noticed it even reached 14.7. But once I unplug it from the charge, it drops to 12.6 and then drops further to 12.4 before further depleting until 10.something. Please, what do I do? I'm so exhausted |
ManAdii: 10:09am On Mar 17 |
Amyah:What battery type are you using? |
dollarnaira: 10:52am On Mar 17 |
ask4bk:You even have time replying. The only thing we see here if fire fire fire; risk risk risk. But we all: put our phones in our pocket with built in lithium ion that most run away from. Sit on fuel tank in our cars Plug in sockets with 220v even beside a new born baby. See bike men sit close to their fuel tanks. see ceiling fans running over our heads. But when we see solar and lithium ( ion or phosphate) we start running here and there screaming risk and fire because of selected few that abused their system. This thread is not for validation or personal opinion of selected few. Make your research, test, and go for what works for you and you. OGA, USE YOUR S.. 6 Likes |
dollarnaira: 11:47am On Mar 17 |
Amyah: I see battery death. Typical way a lead acid behaves when going bad. 2 Likes |
Ifexabc: 2:03pm On Mar 17 |
Good Morning.. Our product offerings include, but are not limited to, the following: JA 580 Mono Solar s - Bifacial 5kWh/48V BYD/Leoch Lithium Batteries 11.7kWh/48V Leoch Lithium Batteries 5kWh High Voltage Deye Batteries String Inverters-25KW/50KW/100KW/120 Goodwe brand Hybrid Inverters 5KW - 48V - single phase - Voltronic Hybrid Inverter 8 & 12kW - 48V - 3 phase - Deye Hybrid Inverter 20 & 50kW - 160V-800V - 3 phase - high voltage - Deye.. We believe that these high-quality products would be an excellent fit for your business. We would be thrilled to have you our list of esteemed dealers and work together to expand the reach of these products. Please let us know if you are interested in exploring this partnership further. We also sell Perkins, and MWM Gas Generators ranging from 15kva-2500kva... 580w s = ₦150,000 EACH (10yrs Warranty and 25yrs Lifespan)
|
Anyone0455: 2:13pm On Mar 17 |
Amyah: Kind of experiencing same thing as you’re tho mine will charge to 13. Something and drop to 12.6 then But since mine is 900kva with two batteries I want to upgrade the inverter to 2.5kva before I start troubleshooting plus also the inverter charges the battery slowly |
HeavenlyBang(m): 2:22pm On Mar 17 |
EVs are the future. New 1MW flash charging unveiled today. 1000v, 1000A. 4 Likes |
HeavenlyBang(m): 2:23pm On Mar 17 |
Amyah: Let me guess, tubular battery? |
maklelemakukula(m): 2:33pm On Mar 17 |
isangjohnson:Good day isiang, I want to make a purchase of >100kg from Alibaba, please what shipping agent do you usually use yourself that is reliable and affordable, and what's the average time it takes your goods to arrive |
justcallmenuel(m): 3:35pm On Mar 17 |
Olamlag:Dm me I will give you good price for this, and the best |
justcallmenuel(m): 3:37pm On Mar 17 |
1pcs of 10kwh felicity lithium battery. 12pcs of 350w Gbm solar s 1pcs of 5kva 48v felicity inverter 1pcs of 80A felicity mppt charge controller Cables All items are ready for delivery to Berger, Lagos State.. Call/whatsapp me on 08168986461 to place your orders !
|
justcallmenuel(m): 3:38pm On Mar 17 |
16mm 2 core solar cable available, #7,500 per metre.. Call/whatsapp me on 08168986461
|
Iinnov8: 3:42pm On Mar 17 |
Anyone0455: First off, what you have is 0.9kva or 900va inverter, not 900kva like you stated. Secondly, if your inverter batteries are draining that fast already, getting an inverter as large as 2.5kva will make it worse as the inverter will consume significant energy to power itself - it could be as much as 40w Finally, your batteries may not be bad per se. You may just have an under-charging problem. Inverters with charging function do not charge batteries optimally. Most times, they undercharge your batteries. Your lead acid batteries should bulk charge to 14.4-14.6v (full charge), then float down to 13.6v if left idle. But most inverters will charge to 13.5v, then stop charging and indicate as battery full when the battery isnt. The result is this sharp drop in voltage you currently experience and you wont get good backup time from the batteries. And if this situation continues, the batteries will begin to experience sulphation on the plates, leading to more damage. What you need is an external charge to continue charging the batteries after the inverter stops its own charging. Also use a multimeter to get the voltage readings of your batteries while at it. Meanwhile, where is your location? How many batteries do you have? And in what way are they connected - 12v or 24v? 1 Like |